1. Apc Battery Back Ups Es 750 Manual
  2. Apc Back-ups 750 Es Manual

View and Download APC SMART-UPS 750 instruction manual online. User Guides and Service Manuals. Manuals APC SMART-UPS 750 APC SMART-UPS 750 User Manual. Size: 2.56 Mb. 1 Back = Page 2 = 2. Reduce the load on the UPS by unplugging equipment and resetting the circuit breaker (on the back of UPS) by pressing the. Back-UPS ES 750. Users Guide 2. W w w.apc.com. Connect Battery For safety, the Back-UPS ES is shipped with one battery wire disconnected. The UPS will not operate until the wire is connected to the touch-safe battery terminal. Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower 1 Overview Product Description The APC® by Schneider Electric Smart-UPS® 750-3000 VA 120/230 Vac Tower is a high performance Uninterruptible Power Supply (UPS). It provides protection for electronic equipment from utility power.

Back-UPS ES 750 User’s Guide 1 2 3 Connect Battery Power On and Install Software Surge Protection These outlets provide full-time protection from surges even if the Back-UPS ES is switched OFF. Plug your printer, fax machine, scanner, or other peripherals that do not need battery power into these outlets. Place the Back-UPS ES to avoid.

Size:Download

English

APC Smart-UPS®

750/1000/1500 VA

100/120/230 Vac

2U Rack-Mount

Uninterruptible Power Supply

990-1194C07/2008

Introduction

The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags, and surges from reaching your computer and other valuable electronic equipment. The UPS filters small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line. The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is discharged.

1:INSTALLATION

Read the Safety Instruction sheet before installing the UPS.

Unpacking

Inspect the UPS upon receipt. APC designed robust packaging for your product. However, accidents and damage may occur during shipment. Notify the carrier and dealer if there is damage.

The packaging is recyclable; save it for reuse or dispose of it properly.

Check the package contents. The package contains the UPS, the front bezel, the rail kit, and a literature kit containing:

Product documentation and safety information

CD-ROMwith additional user manual language support and safety information

PowerChute® CD-ROM(120V/230V models only)

Serial and USB communication cables

Apc Battery Back Ups Es 750 Manual

Two IEC jumper cables and one plug adaptor (230V models only)

The UPS is shipped with the battery disconnected.

Rail Installation

Install the rails following instructions in the rail kit.

Mounting rails are supplied for the standard 4-postrack.Two-postracks require only the mounting brackets.

2

Ear Mounting Locations:

1.

Standard

2.

Optional (1.4' setback)

3.

2-postrack (5' setback)

13

1

Positioning the UPS

Place the UPS where it will be used. The UPS is heavy. Select a location sturdy enough to handle the weight.

Do not operate the UPS where there is excessive dust or the temperature and humidity are outside the specified limits.

0º40ºC (32º-104ºF)

PLACEMENT 0-95%Relative Humidity 2.5 cm (1 in.)

Mounting the UPS in a Rack

The UPS is heavy. To lighten it, you may remove the battery before mounting the unit in the rack (Steps 1 and 2).

Step 1

Step 2 Caution: The battery is heavy.

Step 3

Ups

Install the UPS at or near the bottom of the rack (Step 3).

Check to ensure the rack will not tip after installing the UPS into the rack.

2

Installing and Connecting the Battery and Attaching the Front Bezel

Step 1

Step 2

Step 3

Step 4

Connect battery plug to UPS. Tuck white battery cord into space above connector.

Connecting Equipment and Power to the UPS

SMART-UPS REARPANEL

100/120V Models

120V Model Only: Site wiring fault indicator

230V Models

3

1.Connect equipment to the UPS. Note: Do not connect a laser printer to the UPS. A laser printer draws significantly more power than other types of equipment and may overload the UPS.

2.Add any optional accessories to the Smart-Slot.

3.Using a power cord, plug the UPS into a two-pole,three-wire,grounded receptacle only. Avoid using extension cords.

100V/120V models: The power cord is permanently attached to the rear panel of the UPS. The INPUT plug is a NEMA5-15P.

230V models: The power cord is supplied by the customer. Connect ground leads to the TVSS screw (optional). To make the connection, loosen the screw and connect the surge suppression device’s ground lead. Tighten the screw to secure the lead.

4.Turn on all connected equipment. To use the UPS as a master ON/OFF switch, be sure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.

5.To power up the UPS press the button on the front panel.

The UPS charges its battery when it is connected to utility power. The battery charges to 90% capacity during the first four hours of normal operation. Do not expect full battery run capability during this initial charge period.

120V Models: Check the site wiring fault LED located on the rear panel. It lights up if the UPS is plugged into an improperly wired utility power outlet. Refer toTroubleshooting in this manual.

6.For additional computer system security, install PowerChute® Smart-UPSmonitoring software.

BASICCONNECTORS

Serial Port

USB Port Power management software and interface kits can be used with the

UPS. Use only interface kits supplied or approved by APC.

Use an APC supplied cable to connect to the Serial Port. DO NOT use a standard serial interface cable since it is incompatible with the UPS connector.

Apc Back-ups 750 Es Manual

Both Serial and USB Ports are provided. They cannot be used simultaneously.

TVSS Screw The UPS features a transient voltage surge-suppression(TVSS) screw for connecting the ground lead on surge suppression devices such as telephone and network line protectors.

When connecting grounding cable, disconnect the UPS from utility power.

4

SMART-UPS FRONTPANEL

Power On

Power Off

Online

The online LED illuminates when the UPS is supplying utility power to

the connected equipment. If the LED is not lit, the UPS is either not

turned ON, or is supplying battery power.

This LED illuminates to indicate the UPS is compensating for a high utility voltage.

This LED illuminates to indicate the UPS is compensating for a low utility voltage.

When the on battery power LED is lit the UPS is supplying battery power to the connected equipment. When on battery, the UPS sounds analarm—fourbeeps every 30 seconds.

The LED illuminates and the UPS emits a sustained alarm tone when an overload condition occurs.

5

Replace Battery

Battery

Disconnected

Automatic Self-Test

Manual Self-Test

Failure of a battery self-testcauses the UPS to emit short beeps for one minute and thereplace battery LED illuminates. Refer toTroubleshooting in this manual.

The replace battery LED flashes and short beep is emitted every two seconds to indicate the battery is disconnected.

The UPS performs a self-testautomatically when turned on, and every two weeks thereafter (by default).

During the self-test,the UPS briefly operates the connected equipment on battery.

If the UPS fails the self-test,thereplace battery LEDlights and immediately returns to online operation. The connected equipment is not affected by a failed test. Recharge the battery for 24 hours and perform anotherself-test.If it fails, the battery must be replaced.

Press and hold the button for a few seconds to initiate theself-test.

On Battery Operation

The Smart-UPSswitches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button (front panel) to silence the UPS alarm (for the current alarm only). If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is exhausted.

If PowerChute® is not being used you must manually save your files and turn off the computer before the UPS fully discharges the battery.

DETERMININGONBATTERYRUNTIME

UPS battery life differs based on usage and environment. It is recommended that the battery/batteries be changed once every three years. See the APC web site, www.apc.com, for on battery run times.

6

3:USERCONFIGURABLEITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OR OPTIONALSMARTSLOT

ACCESSORY CARDS.

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Automatic Self-Test

Every 14 days

Every 7 days

This function sets the interval

(336 hours)

(168 hours),

at which the UPS will execute

On Startup Only, No

a self-test.Refer to your soft-

Self-Test

ware manual for details.

UPS ID

UPS_IDEN

Up to eight characters to

Use this field to uniquely

define the UPS

identify the UPS, (i.e. server

name or location) for network

management purposes.

Date of Last Battery Re-

Manufacture

Date of Battery Replace-

Reset this date when you

placement

Date

ment

replace the battery module.

mm/dd/yy

Minimum Capacity Before

0 percent

15, 25, 35, 50, 60, 75, 90

The UPS will charge its bat-

Return from Shutdown

percent

teries to the specified percent-

age before return from a shut-

down.

Voltage Sensitivity

Brightly lit: UPS is set to

To change the UPS sensitiv-

The UPS detects and reacts

high sensitivity.

ity, press the voltage sensitiv-

Dimly lit:

ity button

(rear panel).

to line voltage distortions

UPS is set to

Use a pointed object (such as

by transferring to battery

medium sensitivity.

a pen) to do so.

operation to protect the

Off:

UPS is set to

connected equipment.

You can change the sensitiv-

low sensitivity.

Where power quality is

ity level through PowerChute

poor, the UPS may fre-

software.

quently transfer to battery

operation. If the connected

equipment can operate

normally under such condi-

tions, reduce the sensitivity

setting to conserve battery

capacity and service life.

Alarm Delay After Line

5 second delay

30 second delay, At Low

To avoid alarms for minor

Fail

Battery Condition, No

power glitches, set the alarm

delay.

Shutdown Delay

20 seconds

0, 60, 120, 240, 480, 720,

Sets the interval between the

960 seconds

time when the UPS receives a

shutdown command and ac-

tual shutdown.

7

NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OR OPTIONALSMARTSLOT

ACCESSORY CARDS.

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Low Battery Warning.

Brightly lit: Low battery

The low battery warning

PowerChute interface

warning interval is about

beeps are continuous when

two minutes.

two minutes of run time re-

software provides auto-

Dimly lit:

Low battery

main.

matic, unattended shut-

warning interval is about

You can change the warning

down when approximately

five minutes.

two minutes (by default) of

interval default setting

Off:

Low battery

battery operated run time

through PowerChute soft-

warning interval is about

remains.

ware.

eight minutes.

Possible interval settings:

5, 7, 10, 12, 15, 18 min-

utes.

Synchronized Turn-on

0 seconds

20, 60, 120, 240, 480,

The UPS will wait the speci-

Delay

720, 960 seconds

fied time after the return of

utility power before turn-on

(to avoid branch circuit over-

load).

High Transfer Point

100V:

100V:

Samsung r530 graphics drivers download. To avoid unnecessary battery

108VAC

110, 112, 114VAC

usage, set the high transfer

120V:

120V:

point higher if the utility volt-

age is chronically high and

127VAC

130, 133, 136VAC

the connected equipment is

230V:

230V:

known to work under this

condition.

253VAC

257, 261, 265VAC

Low Transfer Point

100V:

100V:

Set the low transfer point

92VAC

86, 88, 90VAC

lower if the utility voltage is

120V:

120V:

chronically low and the con-

nected equipment can tolerate

106VAC

97, 100, 103VAC

this condition.

230V:

230V:

208VAC

196, 200, 204VAC

8